Determination of Load Capacity

Know what your service can carry before you add to it.

Chargers, a heat pump or a new kitchen line all start with the same question. We read what the facility has actually drawn over a year, add the new load the way the code requires, and give you the answer as fits, tight or short.

DeterminationSpecimen

Determination of Load Capacity, Main Service

12 months of utility interval data
Existing, measured
220 A
With the new load
360 A
Verdict

Fits, with 40 A to spare on a 400 A service.

Reviewed and sealed by a licensed Professional Engineer

How Capacity Is Counted

The code recognises two ways to establish the load already on a service, and they can give very different answers for the same facility.

Over the topStill spareIt fitsThe service you already haveExisting load, calculatedEVERY LOAD, ASSUMED AT ONCEExisting load, measuredWHAT THE FACILITY ACTUALLY DREWTHE LOAD YOU WANT TO ADD, THE SAME ON BOTH SIDES

A shape, and it describes no particular facility. How much room a measurement shows is a property of the facility.

Calculated, or measured

An Article 220 calculation adds up the equipment and applies demand factors. It has to assume a great deal of that equipment runs at once, because it has no record of what actually did.

NEC 220.87 starts from the highest demand the facility actually recorded over a year. A service that looks full on paper often carries far less than its calculation says.

We use the measured method wherever the facility has operated long enough to have a record, because it is the one that describes the facility as it is.

What Decides the Answer

The year's highest demand

The existing load is the busiest 15 minutes the service carried in 12 months, read from the utility's own record or, where there is none, from 30 days on the panel.

The code's margin

The 2023 NEC, which California has adopted, adds 125% to the recorded peak. The 2026 edition keeps that margin and numbers the section 120.87. The calculation cites whichever edition the authority reviewing the permit has adopted.

What you are adding

The new load is calculated under the code's own rules for that equipment, at its full rating unless a listed load management system limits it.

How We Do It

  1. Utility account connected12 months of 15-minute demand, with the tariffHighest demand each month, in amps0100200300JFMAMJJASOND400 A ratingPreliminary Capacity ReportHarlow Street MotorsMeasured peak220 ARating400 AWith the chargers360 AVerdictFitsNo seal, so not submittable.01 Utility data

    We read 12 months of your utility's interval data first, with no visit, and that gives a first answer.

  2. MAIN 400 ASchedulePanel MDPHarlow Street Motors400 A, 208Y/120 VCKTSERVESBREAKER1Rooftop unit 150 A2Rooftop unit 250 A3Showroom lighting60 A4Lot lighting30 A5Service bay lifts60 A6Air compressor40 A7Offices, parts room100 A8Water heater40 A9Car wash bay40 A10Fire alarm, egress20 A02 Panel record

    We write the panel down circuit by circuit. Sensors go on only where the utility data cannot settle it.

  3. 360 AExisting load plus the chargersMeasured peak220 A125% of it+55 A4 chargers+85 A40 A to spare400 AratingFits03 Calculation

    We add the new load to the measured peak under NEC 220.87 and set the total against your rating.

  4. DETERMINATIONThe service supportsthe chargers.Existing, measured220 APer 220.87, x 125%275 AChargers+85 AHeadroom after40 AReviewed and sealed by a licensed P.E.Harlow Street MotorsE-000CALCULATION1 Maximum demand, 12 months220 A2 Line 1 x 125%275 A3 4 EV chargers+85 A4 Total, line 2 + line 3360 A5 Service rating400 A6 Spare, line 5 less line 440 AHarlow Street MotorsE-301SINGLE-LINE400 A mainEV, newExisting feedersHarlow Street MotorsE-101PANEL SCHEDULE1Rooftop unit 150 A2Rooftop unit 250 A3Showroom lighting60 A4Lot lighting30 A5Service bay lifts60 A6Air compressor40 A7Offices, parts room100 A11EV chargers, proposedHarlow Street MotorsE-201BASISDemand recordUtility dataMain breaker 400 AField photoRooftop unit nameplatesField photoCar wash bay loadStated by ownerTransformer impedanceUnverifiedHarlow Street MotorsE-401CERTIFICATIONLICENSEDP.E.SpecimenSignatureDateLicence expiryHarlow Street MotorsE-00104 Review

    A licensed Professional Engineer reviews the calculation and seals it for your permit.

Watch a determination being made →

What You Receive

  1. Preliminary Capacity Report

    The answer from your utility's own data, reviewed by an engineer.

    Not sealed
  2. Stamped Load Study, measured

    The same answer as a calculation sealed for the permit.

    From your utility's records
  3. Stamped Load Study, metered

    Where the utility cannot see the panel. 30 days measured first.

    From 30 days on the panel

Preliminary Capacity Report: No seal, so it is not submittable to an AHJ. It is the same analysis and the same numbers, for planning or a second opinion. Upgrade any time and the $500 comes off.

I'm adding load. Will my panel take it? Start with a year of your own demand.