Power Quality Study

A hot board and failed drives usually share one cause.

Variable-speed drives draw a current that is far from a sine wave, and years of single-phase circuits landed on whichever phase was handy leave the three uneven. Both heat the board and both wear the drives. We meter the board for a week and specify the correction.

DeterminationSpecimen

Power Quality Study, Main distribution board

7 days on a power quality meter
Phase imbalance
14.7%
Harmonic distortion
29.5%
The cause

Harmonic current from the 6 drives heats the neutral, and single-phase circuits landed on phase C heat its bus. The board runs 17 degrees hotter than its neighbours, from one cause.

Reviewed and signed by a licensed engineer under their own licence

Three Phases, Loaded Unevenly

A three-phase board is designed to carry the same current on each phase. Single-phase circuits added over the years rarely respect that.

236 APHASE A198 APHASE B262 APHASE CBeforeIMBALANCE 14.7%230 APHASE A234 APHASE B232 APHASE CAfter the movesIMBALANCE 0.9%CURRENT ON EACH PHASE, IN AMPS. THE DASHED LINE IS THE AVERAGE

Calder Works, the specimen plant in the scrolled story: A packaging plant with six variable-speed lines. The main distribution board, before and after 3 circuits were moved.

Where the imbalance comes from

Phase C carries 262 A and phase B 198 A, an imbalance of 14.7%. Office lighting, the break room and the compressor room lighting were all landed on the heavy phases, one job at a time, and nobody rebalanced.

Moving 3 single-phase circuits brings the imbalance to 0.9%. It is a morning's work for an electrician, and the study says exactly which circuits.

Current That Is Not a Sine Wave

A drive takes power from the supply in pulses, and the pulses add up to current at multiples of the mains frequency. A clamp meter reads the total. A power quality meter reads each part.

22%7%3RD HARMONIC17%6%5TH HARMONIC9%3%7TH HARMONIC4%2%11TH HARMONICBEFORE, 29.5% DISTORTIONAFTER THE FILTERS, 9.9%HARMONIC CURRENT, AS A SHARE OF THE FUNDAMENTAL

The same board. Each harmonic order as a share of the fundamental current, before and after line reactors and a passive filter on the drive section.

What distortion does

29.5% of the current on the specimen board is harmonics. The third harmonic from all three phases adds in the neutral instead of cancelling, so a conductor that should carry almost nothing carries 58 A and runs hot.

Filtered at the drives, distortion falls to 9.9% and the neutral to 14 A. The correction is specified for the plant's electrician, and the board is read again after it.

What It Does Downstream

The board runs hot

Harmonic current heats the neutral and the transformer, and an imbalance heats one phase's bus. The specimen board ran 17 degrees hotter than the boards beside it, and 2 degrees after the correction.

Drives trip and fail early

A drive fed from a distorted, uneven supply runs its own electronics hotter and trips on faults that look random. Two drives failed on the specimen plant in a year.

The neutral carries current it should not

On a balanced board with clean current the neutral carries almost nothing. Third harmonics add in it: 58 A on the specimen board, 14 A after.

The Correction, Specified

Written for your electrician: which circuits move, what goes on each drive feeder, and what the board should read after.

Rebalance the phases

Move 3 single-phase circuits off the heavy phases: Ckt 7, Ckt 11, Ckt 15. After the moves the phases read 230, 234 and 232 A.

Filter the harmonics at the drives

Line reactors on each drive feeder and a passive filter on the drive section, specified to bring distortion under 10%.

What the board should read after

Imbalance under 3%, the neutral under 20 A, and the board within a few degrees of its neighbours.

How We Do It

  1. MAIN 1200 AScheduleRECRecordercollected afterA power quality meter, one weekCurrent on each phase and the neutralVoltage on each phaseHarmonics to the 11thEvery minute, while the lines run01 The board

    We write the board down phase by phase and put a power quality meter on it for a week.

  2. Current on each phaseAverage 232 A. Imbalance 14.7%751502253000 APhase A236 APhase B198 APhase C262 A232 A averagePhase C is 30 A over the average. One bus runs hot, and every motor on the board runs hotter for it.02 The phases

    We read the current on each phase, the harmonics in it and the neutral, and name the cause with its evidence.

  3. The correction, for the plant's electrician1Rebalance the phasesMove 3 single-phase circuits off the heavy phases: Ckt 7, Ckt 11, Ckt 15. After themoves the phases read 230, 234 and 232 A.2Filter the harmonics at the drivesLine reactors on each drive feeder and a passive filter on the drive section,specified to bring distortion under 10%.3What the board should read afterImbalance under 3%, the neutral under 20 A, and the board within a few degrees of itsneighbours.3 circuits moved, line reactors and a filter on the drives. Wattif performs no electrical work.03 The correction

    We specify the moves and the filters for your electrician, with what the board should read after.

  4. The same board, read againImbalance 0.9%. Distortion 9.9%. Neutral 14 A.751502253000 APhase A230 APhase B234 APhase C232 A232 A averageWithin 2 degrees of its neighbours04 After

    We read the same board again after the work, and a licensed engineer signs the result.

Watch a board being read →

What You Receive

  1. The board, measured

    Current and voltage on each phase, the harmonics in the current and the neutral, from a week on a power quality meter.

    From the meter on the board
  2. The cause, named

    The imbalance and the distortion, where each comes from, and what each is doing to the board and the drives.

    Reviewed by an engineer
  3. The correction, specified

    Which circuits move to which phase, what goes on each drive feeder, and what the board should read after.

    Your electrician makes the change
  4. The board after the correction

    The same board read again: imbalance, distortion, the neutral and the temperature against its neighbours.

    After the work

What It Needs

A power quality meter on the board for a week of normal production, and the panel record for every circuit on it, so each single-phase circuit can be placed on its phase. A clamp meter cannot do this; the harmonics only show on an instrument that reads them.

Moving circuits and fitting reactors and filters is electrical work, made by your electrician. Wattif specifies it, reads the board again after it, and a licensed engineer signs the result under their own licence.